SUB STATION
As the power
demand increases in this economical generation of electrical energy, it becomes
more common to have the bigger and bigger power houses. The power houses might
be closer and might be far from load center; in any case it needs transmission
network.
In the midst
of power houses and the consumer many transformation need to be installed that
transformation is called substation.
A substation
is the system which converts one voltage level into on other voltage level and
mostly it convert 11kv into 415v.
Normally the
user do not want high voltage i.e. 11kv, so it need to be convert into 415v by
the means of substation, so we can say that substation is the link between the
generating stations and the consumer main.
Our project
is limited to an office building, so a distribution substation also needs to be
considered. The distribution substation converts the voltage to a small value
for the use of small power consumer. Generally we use 3 phase 4 wire system for
the distribution substation with 415v between the lines and 230v per phase.
i.
DESIGN OF SUBSTATION
For the
design of substation some important points need to be considered
Ø It should be possible to have an easy
and safe access for the maintenance and inception of different equipment.
Ø The layout of the substation should
be such that when the fault comes in power system it isolates the fault as
quickly as possible.
Ø By considering the capacity of
substation, number of feeders etc, lay out of the switch gear is decided.
Ø Power cable and control cable should
be separate.
Ø By considering the IP rating fire
proof switch room and cable should be installed in order to safe from fire
hazards.
ii.
EQUIPMENT USED IN SUBSTATION
The substation consists of the following equipment.
1-Insulators 2-Conductors 3-Reclosing and LT
switch gear
4-Circuit breaker 5-Transformer 6-Protective fuses and
relays
7-switch board 8- metering
1-INSULATORS
For backing of bus bar and live conductors insulators are
used. For the low voltages up to 11kv insulators can be used in stack and can
be mounted horizontally and vertically as per condition but for low voltages
beyond that, insulators are mounted mostly in horizontal configuration.
2-CONDUCTORS
Conductors are of the two types for the substation.
1- Rigid buses of solid conductors
2-Strain buses of cable
These both
types of conductor could be of Aluminum and Copper.
3-RECLOSING AND LT SWITCHGEARS
A recloser is a circuit breaker equipped mechanism, that
trip the breaker after it has been opened due to faulty. We use recloser for
the overhead distribution system relosers are used on a low voltage bus
structure column. While, the switchgear is the combination of disconnect
switches, fuses and circuit breaker used to isolate the equipment in the
substation. The distribution of current on various places depends on the number
of outlet required.
4-CIRCUIT BREAKER
Mostly
vacuum circuit breaker is used for inside the building that’s why we used
vacuum circuit breaker.
Vacuum circuit breaker is a type of circuit
breaker where arcing occurs in a vacuum. This is normally used for medium
voltage application, for high voltage this technology also developed but it is
not common. The opening and closing of current carrying contacts are associated
to arc interruption which is take place in a vacuum chamber of the breaker
which is called vacuum interrupter. The
pressure of vacuum is normally maintained to 10^-6 bars. The contacts are made
up of cu and cr.
4.1-ADVANTAGES OF VACUUM CIRCUIT
BREAKER
Ø Life of vacuum circuit breaker is
longer than the other type of circuit breaker.
Ø Chances of fire hazard are almost
negligible.
4.2-OPERATION
OF VACUUM CIRCUIT BREAKER
The task of any circuit breaker is to
quench arc during current zero crossing, by establishing high dielectric
strength in between the contacts so that reestablishment of arc after current
zero becomes impossible. The dielectric strength of vacuum is eight times greater
than that of air and four times greater than that of SF6 gas. This high
dielectric strength makes it possible to quench a vacuum arc within very small
contact gap. For short contact gap, low contact mass and no compression of
medium the drive energy required in vacuum circuit breaker is minimum. When two
face to face contact areas are just being separated to each other, they do not
be separated instantly, contact area on the contact face is being reduced and
ultimately comes to a point and then they are finally de-touched. Although this
happens in a fraction of micro second but it is the fact. At this instant of
de-touching of contacts in a vacuum, the current through the contacts
concentrated on that last contact point on the contact surface and makes a hot
spot. As it is vacuum, the metal on the contact surface is easily vaporized due
to that hot spot and create a conducting media for arc path. Then the arc will
be initiated and continued until the next current zero. At current zero this
vacuum arc is extinguished and the conducting metal vapor is re-condensed on
the contact surface. At this point, the contacts are already separated hence
there is no question of re-vaporization of contact surface, for next cycle of
current. That means, the arc cannot be reestablished again. In this way vacuum
circuit breaker prevents the reestablishment of arc by producing high
dielectric strength in the contact gap after current zero.
There are two
types of arc shapes. For interrupting current up to 10kA, the arc remains
diffused and the form of vapor discharge and cover the entire contact surface.
Above 10kA the diffused arc is constricted considerably by its own magnetic
field and it contracts. The phenomenon gives rise over heating of contact at
its center. In order to prevent this, the design of the contacts should be such
that the arc does not remain stationary but keeps travelling by its own
magnetic field. Specially designed contact shape of vacuum circuit breaker make
the constricted stationary arc travel along the surface of the contacts,
thereby causing minimum and uniform contact erosion.
5-TRANSFORMER
The function of
transformer in substation is to convert 11kv into 415v.in Pakistan mostly oil
type transformer is used because of its large service life. Oil type
transformer requires minimum maintenance. The main factors which is need to be
considered for the installation of transformers are
A-
Initial
costs
B-
Operating
costs
C-
Reliability
of supply
D-
Served
load
6-PROTECTIVE FUSES AND RELAYS
Normally fuses are
provided with the transformer and other protective devices. Its function is to
protect the transformer.
Protective relays
are also provided for the safety of power system. For the protection of
transformer we use BUCHOLOZ RELAY.
When a fault
occurs in a transformer or the short circuit occur in the transformer then the
pressure inside the oil tank increases and oil starts moving towards
conservators in this passage it also passes through the BUCHOLZ RELAY. The
baffles in the relay get passed by the rushing oil and now the relay will
operate and accordingly it trips the circuit breaker. Now we can remove
transformer for the service.
7-SWITCH BOARDS
Meters, relays
and control equipment are places in a switch board. Two meters i.e. essential
and non essential are placed at the top of relay and bottom of relay
respectively. The control equipments are normally placed between half way
between top and bottom so as to facilitate their operation.
8-METERING
The energy meter
incorporating maximum demand indicators is provided with the incoming HT
supply. An ammeter and volt meter is also provided with the selector switch to
shift across the lines are also fitted in the HT panel. An ammeter and one volt
meter has been also provided with the LT lines.
Good information you shared. keep posting.
ReplyDeletePower Transformers in India | Transformer Manufacturer in India